The Minerva MZX-c range of conventional fire
detection control panels are designed to be both
installer and user friendly. A high degree of flexibility
and programmability allows the systems to be
customised without the need for any configuration
software. The range consists of 2, 4 and 8 zone
panels together with an 8 zone repeater which is
compatible with the 4 and 8 zone variants. The
matching repeater panel has an inbuilt 240Vac power
supply.
All the units are designed and manufactured to the highest standard and the range is approved by the Loss
Prevention Certification Board (LPCB) to EN54 parts 2 and 4.
Features:
2, 4 and 8 zone versions available.
Supports the complete range of EN54 approved series 600 detectors including photo multi-sensor and
CO multi-sensor.
Supports Tyco twin wire sounders on all eight detection zones.
Drives up to 3 repeater panels (4 and 8 zone panels).
Access to controls via key switch.
Space for 2 x 3.4 A/H batteries providing up to 72 hour standby.
Remote control inputs for class change, alert, evacuate, silence alarms and reset.
Zone 1 configurable for latching or non latching.
Selectable zonal or general alarm sounder operation.
Alert sounder option.
Configurable zone co-incidence for automatic detectors.
Fully monitored fire signalling output.
Single pole volt free change over fire relay output.
Single pole volt free change over fail safe fault relay output.
Short circuit fire option
Auxiliary 24VDC 250mA power supply output.
Open collector output for buzzer active, disablement active and evacuate active.
Earth fault monitoring.
Zone/Output disablement for each zone, fire signal output and all sounders.
Buzzer disable feature.
One man zone test.
One man sounder test.
Automatic fire detector and manual alarm call point fire event discrimination.