The MIO800 is a general purpose interface module for use with MX Technology fire detection systems.
It allows multiple input and output connections to be made between external equipment and the MX Digital loop.
Three inputs and four outputs are provided. Each input and output can be programmed independently using the MX Consys configuration tool to provide customised functionality.
An IP55 rated D800 style housing is used as the standard enclosure with the option of a DIN-Rail mounting kit for in-cabinet installations.
Features:
Connects directly to the MX Digital loop
Loop powered does not require a 24V supply
Provides three digital inputs
Normally open or normally closed inputs
Inputs monitored for open circuit or short circuit faults
Style B (short circuit gives an alarm) or Style C (short circuit gives a fault) selectable for inputs
On-board LED illuminates when any of the three inputs alarm
Window in the D800 housing lid gives visibility of the on-board LED
Provides four digital outputs
All four outputs can drive a self-powered high voltage relay HVR800
Two outputs have both volt free change-over contacts and HVR Drivers
D800 IP55 housing or DIN-Rail mounting
Inputs and outputs are independently controlled by the MX Technology system configuration